Category Archives: EuroSun2008-4

Building categories

1.1. LE-OLD

There is no official definition of specific goals and figures for low energy buildings. Some attempts have been made to define a low-energy building. In general, it refers to a building built according to special design criteria aimed at minimizing the building’s operating energy [11].

500

Подпись:Подпись:450

400

350

300

250

200

150

100

50

0

Figure 1 gives an overview of the estimated energy consumption of the building stock and the energy target for aggregate net energy demand for different building types in kWh/(m2 a) [5,12]. It shows that the new building regulation requires a drastic reduction in energy consumption (i. e. 50% in commercial buildings and 31% in office buildings). In Germany, the ‘lean building’ has been defined with specific primary energy consumption of 100 kWh/(m2a) [14]. The new energy labelling system will help to categorize the levels of energy use in buildings [15].

The heat recovery from PV systems

The photovoltaic system plays an essential role in this building, not only for the production of electricity (see 3) but one of the strategies of this building in winter is to recover and use the heat produced in the PV system and used in winter time, according Figure 4. There are several possible situations which can be used in this system.

In winter the user during daytime, open the vents which connect the interior of the building with the space between the PV and the wall. By natural convection, the air enter through this vent, is heated and return to the building, during nigh time to user has to close this circulation closing the vents.

image348

Figure 5, presents the measured temperatures in the vents (upper and lower vent) as also in the room, and in synthesis it is possible to see that in an winter day the incoming temperatures from the PV system are around 30°C in a sunny day and could achieve the 37°C.

Edificio Solar XXI — INETI

Temperatures do Sistema de Recuperaqao de Calor dos Modulos PV

image349

Margo 2007

Fig. 5.Temperatures in the vents from the PV system.

Perspirable Building

The perspirable building has a perspiration function by simulating the mechanism of concentration gradient, osmotic pressure, capillarity, mechanical energy and electric potential difference controlling perspirable action in a human body. The perspiration function in the building manifests itself with the construction of perspirable roof and wall (window) using thermo-sensitive hydrogel as a new material. The thermo-sensitive hydrogel is absorption/desorption resin with thermal reversibility; water is absorbed below a specific sense temperature and desorbed over the temperature, like perspiration in a human body. It is the evaporative cooling performed not by water sprinkling onto the roof but by the autonomous perspirable function of the wall.

Validation of the CFD hypothesis for the laminar situations

Подпись: Figure 2. Comparison of Nu for symmetric uniform wall heat fluxes

A wide number of simulations have been carried out (381); some of them have been used to validate the CFD model and the numerical assumptions with experimental results and previous authors. In the case of laminar situations, maximum deviations of 10 % have been obtained in the prediction of average Nusselt numbers and mass flow rate. In figure 2, a comparison between the numerical values of Nu and the mathematical expressions of different authors is showed [1,13,14].

1.1. New correlations for Nu and mass flow rates

Подпись: + image105 Подпись: -0.5 Подпись: (1) (2)

Using the CFD simulations and applying a non linear regression based on iterative estimation algorithms (through the SPSS software) different correlations for the cases with asymmetric isofluxes have been obtained. In the case of the Nusselt numbers, the new correlations are based on the expressions of Bar-Cohen and Roshenow [1], but including the effect of the asymmetry (qwc / qwh), being qwc and qwh, the hot and cold wall isofluxes respectively:

Where: Nuh ,fw is the average Nusselt number for the hot wall; Nuc t is the average Nusselt number

for the cold wall. In the case of the mass flow rate, a new correlation for the friction factor has been obtained:

image108
Подпись: (3)

A comparison of these three correlations with the numerically calculated results has shown deviations lower than 6 %. However, some refinements in the equation 2 for situations with low Rayleigh numbers and in equation 3 for high asymmetric cases will be carried in the next future.

Window products

There are a large number of coated and uncoated glass panes available on the market, and all of these can be combined into numerous different window combinations. To help customers select suitable windows among this almost infinite number of glazing combinations, the International Glazing Data Base (IGDB) has been set up by the Lawrence Berkeley National Laboratory in California [12]. The database contains glazing products manufactured by most major glass manufacturers in the world, and their main optical properties are provided, usually together with reflectance and transmittance spectra. It is a complex task to choose the most suitable window for a certain building and location out of all these products. The important parameters for the function of the window vary within wide limits, and if we for example consider the U-value and the g-value, we can see in Fig. 1, that windows with many different values of these parameters are available. Each point in the diagram represents a window made up from two panes found in the IGDB. The figure only includes a small selection of double glazed configurations air filled insulated glazing units. Triple glazed configurations with argon-fill would extend the graph down to U-values of around 0.6 W/m2K. Depending on the function of the window and the type of building, orientation and climate, different combinations of high or low U — and g-values would be the best choice. For optimum performance in a certain situation we may want to look for a window close to one of the corners in the graph. Often a compromise has to be selected since summer and winter may require quite different properties for optimum performance.

з

image152

1.4

1.2

image15310 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

g-value

Fig. 1. U-value vs. g-value for over two thousand Fig. 2. Visible transmittance vs. g-value for twelve double pane windows. double pane windows.

These considerations lead to the conclusion that we often would want windows with variable optical and thermal properties depending on the time of year, time of day or weather. The electrochromic coatings mentioned in the introduction bring us a few steps towards this situation. Existing products on the market or prototypes made up in the laboratory show that we can identify window products with variable optical properties. A few examples are shown in Fig. 2 where the product specifications have been plotted in a graph with tv versus g-value. Table 1 gives a brief description of the double glazed windows presented in this graph. This type of graph is mainly useful for solar control glazing, for which both a low g-value is desired to prevent over-heating and a low Tv-value is desired to prevent glare. The problem is that we also want high tv for the day­lighting and visual contact with the surroundings. Thus, the switchable electrochromic glazing could be the ideal solution. In the graph we can see that the shown optical properties can be varied within quite wide limits, which makes it possible to optimize the performance for different weather conditions and according to the needs of the occupants. The non-physical area in the graph is due to the fact that around 50% of the solar radiation is visible light.

Table 1. Description of pane configuration used for double pane windows in Fig. 2

Hard Low-E

SnO2 low-e coating on surface three combined with an outer floatglass pane.

Soft Low-E

Single silver coating on surface three combined with an outer float glass pane

Soft SC

Double silver coating on surface two combined with an inner float glass pane.

Abs. SC

Absorbing outer pane combined with an inner float glass pane

SS clear

Solid state electrochromic film in its clear state on surface two combined with an inner float glass pane.

SS dark

Solid state electrochromic film in its dark state on surface two combined with an inner float glass pane.

Foil/float C

Electrochromic plastic foil in its clear state on the inside of an outer float glass pane combined with an inner float glass pane.

Foil/float D

Electrochromic plastic foil in its dark state on the inside of an outer float glass pane combined with an inner float glass pane.

Foil/Low-E C

Electrochromic plastic foil in its clear state on the inside of an outer float glass pane combined with an inner low-e pane.

Foil/Low-E D

Electrochromic plastic foil in its dark state on the inside of an outer float glass pane combined with an inner low-e pane.

MH trans.

Metalhydride electrochromic film in its clear state on surface two combined with an inner float glass pane.

MH refl.

Metalhydride electrochromic film in its reflective state on surface two combined with an inner float glass pane

3. Method

3.2. Energy simulations in WinSel

The energy simulations were performed using WinSel, a simulation tool developed at Uppsala University [7,8]. The program was designed as a window selection and energy rating tool, hence the acronym WinSel. Hourly climate data of direct and diffuse radiation and temperature are used for hour-by-hour calculations of the annual energy balance. Window in-data are the total solar energy transmittance (g-value), the thermal transmittance (U-value), and parameters controlling the

angular dependence of the g-value. The building input data are limited to the thermal mass dependant time-constant and the balance temperature. The balance temperature is defined as the outdoor temperature when neither cooling nor heating is required to maintain the set indoor temperature. Consequently, the heating season is defined as all hours of the year when the outside temperature is lower than the balance temperature. The cooling season is defined with a temperature swing allowing the indoor temperature to increase to a value above the set indoor temperature before any cooling is considered.

Exergetic analysis of the EACS

The notion of exergy, also called availability, was introduced at the end 19th century by Georges Gouy. This concept merge both the first and second law of thermodynamics and then allow to take into account the amount of energy transfer during a process but also the quality of this energy transfer. The exergy could be physically defined as the maximum mechanical work that a system could provide during a transformation between a thermodynamic state and a reference state. This means if a system is in thermodynamic non-equilibrium compared to the ambiance, the maximum work it could provide to reach back ambient conditions is the exergy; the difference between the achieved work and the exergy between the two states being the losses or irreversibilities. In this case, the exergy is positive; a negative exergy meaning that work should be provided to the system to reach back the reference state. Exergy is a state function and is defined as

e = (h — h°)-T0 (s — s0) (9

de = dh — T0ds

the indexes "0" referring to the reference state. For driving cycles, the reference state is conventionally the standard conditions, T0 = 15°C, P0 = 1bar. In addition, in the case of vapor evolving in a closed system, the only equilibrium condition compared to the ambient is the temperature condition. Indeed at equilibrium the system will reach the same temperature than the

ambient. However the equilibrium pressure will be the saturation pressure. For such system the reference state is T0 = 15°C, P0 = Psat (T0 ) . For driving cycle this definition is convenient since

this reference temperature is closed to the cold source temperature of the cycle, providing a very small or almost zero exergy loss at the condenser. Indeed, even though a large amount of energy is lost to the ambient, the quality of this energy is quite poor.

In our trithermal air-conditioning cycle, the hot source is the hot water previously heated up by solar collectors. The useful effect occurs at the cold source e. g. the water to cool down (for room air-conditioning) while the sum of those two previous heat quantity is discharged to the ambient through the condenser which is the medium temperature source of the cycle. Similarly to what happens at the condenser for a driving cycle, this significant amount of energy has a poor quality in regards to the targeted effect (cool down compared to ambient). Consequently, an almost zero exergy loss should be requested at this component. In addition the useful effect at evaporator occurs close to 15°C (tow — tiw «12 -18) providing an almost zero exergy variation for cooled

water and almost 100% of losses at the evaporator. All these conditions show that the usual reference state for driving cycles is not suited to air-conditioning cycles. Consequently in this study the reference temperature will be the ambient temperature Tciw at the condenser side. For the refrigeration cycle, the reference pressure will be the saturation pressure at T0 for propane and for secondary cycles (generator, condenser, evaporator) it is the atmospheric pressure (P0 = 1bar).

From an energy point of view the quality of a compression air-conditioning cycle is determined by the global COP as

COP = Qe (10)

comp, global p

1 comp, a

For an ejector based air-conditioning cycle this global COP would then be:

COP, c„b,, = P &+ Q (II)

pump, a sol

With subscript “a” for “absorbed” and Qsol the useful thermal power received by collectors.

However it could be convenient to define cycle based COP in order to eliminate mechanical efficiencies of components which may change significantly according the technology, power, etc…, and also to eliminate the source of heat supply. Indeed, in the proposed cycle solar collector are used to heat up the water but other low grade energy sources could be used to provide this energy; and in this case the way of calculating the energy transfer between the water and a source would be different or it would use very different efficiencies. Consequently to be more general, the concept of cycle based COP is used in this analysis:

COPcomp = PQ^ (12)

comp


Qe

 

COP =

e P

 

(13)

 

-Qw. g + Qw

 

These purely energy criteria are not satisfactory to make a relevant comparison between both systems. Indeed for the compression system the energy input is purely mechanical and then this energy is actually a pure exergy, while the ejector system uses primarily thermal energy which does not have the same exergetic value than a mechanical energy. Therefore, in order to compare

Подпись: ew,g = (Qw,g + Qw,sup) I 1 Подпись: T 0 T Подпись: (14)

both systems on the same objective basis, these COP should be turned into exergetic COP. For the compression system it is obvious because the compression power is purely exergy while for the ejector system Qw should be replaced by its exergy equivalent. An easy way of calculating this exergetic value would be to consider the secondary water as a perfect source delivering a thermal power Qwg at a certain temperature T and using the Carnot factor:

This method may also be used for condenser or evaporator and was used in literature [3]. However this provides not accurate results since the water temperature varies and then it is not a perfect source. In this way the real exergy flux through the generator is used since all secondary cycles (generator, evaporator, condenser) are fully computed in this work:

ew, g = mgw (ew,0 — ew,, )g +amgw (ew,0 — ew,, LP (15)

In addition as proposed in literature an exergetic value of Qe should be used in exergetic COP.

image221 Подпись: (16) (17)

This definition is not used in the current analysis because the useful effect is not mechanical such as in driving cycles/machines but thermal. Such definitions are not relevant since the exergetic value of Qe is very low giving even lower COP and not relevant to compare with classical COP. Consequently it is proposed to compare COP for a same thermal effect at evaporator:

Results are presented in the table 2. It is seen that in an energetic point of view, the ratio between the COP obtained for a conventional compression system and the EACS is very high (18.42 to 29.9). But the ratio of exergetic COP is noticeably lower, with values of around 3.4 to 5.7. It is thus important to highlight that both kind of systems are more comparable in an exergetic point of view, and this definition points out the valorization of the low grade energy. For Tciw=28.4°C, COPej and

COPe undergo the same increase of 6.6 % when the subcooler is used. For Tciw=29°C, COPej

and COPe decrease both of 29%. Note that a comparison between two cases at different Tciw is not

possible in an exergetic point of view, because the chosen reference T0 used for the exergetic analysis is equal to Tciw and thus varies with the considered case.

Table 2: COP and COPex comparison of the EACS and vapor compression cycle, for a=0.13, with and without the use of the subcooler. * denotes a working with regenerator using (P>0)

T (°C)

cm

COP

comp

COPjj

COPex

comp

COPex

e

COP COP.

comp ej

COPex COPex

comp ej

with subcooler

28,4

8,65

0,4327

7,59

2,2466

19,98

3,38

29*

8,59

0,2878

8,59

1,5068

29,9

5,7

without subcooler

28,4

7,64

0,4057

7,64

2,1066

18,83

3,63

29

7,47

0,4056

7,47

2,123

18,42

3,52

3. Conclusion

A detailed rating modeling of the EACS was presented. It was seen that the subcooler can have either beneficial or harmful effect on performances. The advantage of using of a regulator is clearly demonstrated. Moreover, reducing the system performances to an optimization of the ejector entrainment ratio is not judicious. The whole cycle must be taken into account. Finally, a first step of the exergy analysis of the EACS emphasized the more relevant comparison with a conventional vapor compression system. A more detailed exergetic study is in progress to determine the distribution of irreversibilities in the cycle and its variation with different parameters.

References

[1] W. Pridasawas and P. Lundqvist, A year-round dynamic simulation of a solar-driven ejector refrigeration system with iso-butane as a refrigerant, International Journal of Refrigeration, Vol. 30, 2007, 840-850.

[2] G. K. Alexis, E. K. Karayiannis, A solar ejector cooling system using refrigerant r134a in the Athens area, Renewable Energy, Vol. 30, 2005,1457-1469.

[3] W. Pridasawas and P. Lundqvist, An exergy analysis of a solar-driven ejector refrigeration system, Solar Energy, Vol. 76, 2003, 369-379.

[4] A. Hemidi, Y. Bartosiewicz, J. M. Seynhaeve, Ejector air-conditioning system: cycle modeling, and two — phase aspects, Heat 2008 conference, Vol. 2, 421-428.

[5] A. Hemidi, Y. Bartosiewicz, J. M. Seynhaeve, Modeling of an ejector air-conditioning system: sizing and rating tools, IIR conference, 2008.

Review of the Results

The main problem with regard to the performance of the absorption chiller is that it does not reach the projected COP. The following reasons can be found:

• The required temperature for driving the chiller is not provided constantly (see Error! Reference source not found.).

• The re-cooling temperature is mostly at about 28° C and not at 27° C as planed (see Error! Reference source not found.). According to the manufacturer’s characteristics for the machine this causes a performance loss of 10 to 20 %.

• In simultaneous operation of the compression chiller the required flow rate in the cold-water circuit is not achieved.

• The cold-water temperature is lower than planned.

Подпись: Stunden im Jahr Fig. 6. Integrated frequency curves of the temperatures of the driving and re-cooling circuit.

The integrated frequency curves for the temperatures in the driving and re-cooling circuits are shown in figure 6. The minimum required temperature of 75° C in the supply line of the driving circuit is reached for about 3,600 hours of almost 5,000 hours of total operation. That’s nearly 75 % of the time. Only for 2,000 hours a temperature of over 80° C is achieved, less than half of the operation time. The temperature for the supply line of the re-cooling circuit is always higher than 27° C, the temperature is quasi-constant at 28° C.

The parasitic energy consumption of the solvent pump and the refrigerant pump is independent from the refrigerating capacity. Therefore, the total COP declines and the primary energy coefficient and the carbon dioxide emission of the chiller rise disproportional.

The demand of electric energy of the installed absorption chiller is very high compared to other products. Comparable products from other manufactures only need a tenth of the electric connected load. Solely the reduction of the electric energy consumption of the absorption chiller itself to this level would reduce the primary energy coefficient to the level of the compression chiller. The emission of carbon dioxide would fall far below the level of the compression chiller.

4. Optimisation

To improve the conditions for the operation of the absorption chiller several changes where developed and partly realized. For a more constant heat supply additional storage capacity was installed. This storage is reserved for the wood pellet combustion unit. So the existing storage capacity can be used only for the solar collectors. At the same time three bigger units replaced the four wood pellet boilers. The total output of the boilers rises from 128 to 168 kW.

The cold-water outlet temperature will be adjusted according to the demand. Because of the strong power loss of the absorption chiller when the cold-water outlet temperature falls below 9° C, the temperature will be raised to 10° C in times where no de-humidification is needed. This temperature is sufficient for sensible cooling of the air. The cold-water outlet temperature is lowered to 6 to 8° C only in times with high external humidity loads.

To supply the required re-cooling temperature minor improvements to the hydraulics where implemented in 2006 already. However, these improvements did not show any effects in 2007. Further investigations where undertaken to find the reasons. The result was that the control strategy for the re-cooling pumps had to be optimized.

Furthermore, there is the consideration to run the absorption chiller solely by solar heat. The very high consumption of electric energy of the absorption chiller could be only reduced by a complete replacement with another machine.

Estimation of the available roof area

The available roof area is the sum of the areas that are suitable to install PV panels. These are the areas where incident solar irradiation is high. Since tall buildings are very rare in Portugal and neighboring buildings are usually far from school buildings their shading effect was neglected. In pavilion schools (flat roofs) the available area is equal to the total roof area because the PV panels