«Gas billing» according to worksheet G 685 of the DVGW regulations (DVGW, 2008)

For billing, two parameters need to be determined: The volume flow of the fuel gas under standard conditions (T = 0 ° C, p = 1.01325 bar) and the calorific value for billing purposes. The determination of the standard volume flow from the operational flow is done using the procedure described in G 685, taking into account the temperature and atmospheric pressure. At pressures greater than 1 bar, real gas behaviour should be taken into account (G 486). The calorific value for billing purposes is determined from the calorific values of the feed for each billing interval (such as 1 month (special contract customers) or 1 year (residential customers)) in a coverage area (the total area, which is supplied by the GU, not necessarily contiguous). If the calorific values of the feed change over time, then these are determined arithmetically or by volume-weighted methods over the month.

If gases with different calorific values are distributed, then the following, according to G 685 (DVGW, 2008), applies:

according to the regional location of the customer. The gas delivered to customers may not deviate in calorific value by more than 2% from the calorific value for billing purposes. To check this, the mean values and the quantity-weighted average in the downstream network are to be determined.

Since worksheet G 486 is particularly applicable due to the admixing of propane and butane as considered in this report, essential aspects are explained below.