Category Archives: EuroSun2008-4

The strategy

Solar availability is quite high in Portugal, even during the heating season. This makes the direct capture of solar radiation (windows), the indirect collection for domestic hot water and space heating (thermal solar system) and eventually energy production (photovoltaics) advised. Large windows are mainly oriented south, increasing the useful solar gain during winter. Smaller areas are oriented east and west and minimal areas to north. Overhangs on south windows and exterior venetian blinds on all provide solar protection during summer.

High thermal inertia allows control over the inside temperature and combined with night ventilation, prevents overheating. In the bedrooms ventilation should take place in the evenings to avoid drafts during the sleeping period. In all other spaces, all night cooling can be used. High thermal inertia can be achieved by exposing the heavy concrete slab, using brick internal partitions

image446

and preferably applying external insulation to the roof and walls. However, there is still some scepticism among Portuguese builders to the mechanical performance of exterior insulation. Therefore, this proposal uses the traditional double brick wall with cavity insulation.

Insulation levels proposed for the roof (150mm) and exterior walls (100mm) with U-values of 0.23 W/m2.K and 0.32 W/m2.K, respectively, are well below the current regulation requirements. Only a 1m stripe of the perimeter of the floor slab is insulated to allow the core of the house to release heat to the soil during summer. Windows facing south correspond to around 60% of the total glazed area and about 20% of glazed area faces east and another 20% west. Low-emission double glazing can be very effective in colder regions of Portugal, but in most situations standard double glazing is more cost-effective (U-values of 2.9 W/m2.K for standard double glazing and 1.9 W/m2.K for low-emission glazing are considered).

The utilization of solar panels for domestic hot water in new or refurbished buildings (a few exemptions apply) is compulsory under the new thermal regulation. The current proposal extends the solar installation to also cover a significant portion of the heating demand, by increasing the solar panels area and using a low-temperature hydraulic heat distribution (for instance radiant floor). The solar panels are installed facing south, tilted 50° from the horizontal plane, to increase the efficiency during winter. In accordance with the Passivhaus proposal, the active heating and cooling capacity is limited to 10 W/m2. The extra costs of the proposed Passivhaus for Portugal is 57 €/m2 with a payback period of 12 years.

Effect on Building Space Heating and Cooling Loads and Electricity Production

Table 3 presents the electricity production obtained with TRNSYS for the three BIPV curtainwall constructions (scenarios 2, 3 and 4). As it can be observed, systems in Yellowknife and Iqaluit generate approximately the same amount of electricity, whereas the ones in Montreal produce between 4 and 7% less electricity. This can be explained by Yellowknife and Iqaluit greater annual south-facing vertical radiation and lower ambient temperature throughout the year. This table also indicates that scenario 4 is the worst in terms of electricity generation with a production reduced by more than 22% compared to scenarios 2 and 3. The building heating and cooling loads for each one of the 5 scenarios and 3 cities considered are shown in Fig. 6. From this graph, it can be seen that for every city, the lowest heating loads are obtained in scenarios where spandrel is used as the non­vision section, with a difference of only 2 to 3% between the double-glazed and triple-glazed cases (scenario 1 and 5). This variation is small considering that the triple-glazed curtainwall construction of scenario 5 has greater thermal resistance, but this assembly also has a lower solar heat gain coefficient and thus, provide less passive solar heating. The influence of changing from a double-glazed to a triple-glazed system on the space cooling energy requirements is only noticeable for Montreal, but is more important than for space heating with a difference between the two scenarios in the order of 6%. When comparing the substitution of spandrel panels with BIPV curtainwalls, it can be observed that it affects more significantly the space heating load than the cooling load, and the double-glazed systems than the triple-glazed systems. In fact, the heating load increases by 8.9-10.6% when going from scenario 1 to 2 and only by 4.6-5.3% and 5.6-6.3% when going from scenario 5 to 3 and 5 to 4, respectively.

Table 3. Annual DC electricity production for vertical curtainwall assemblies.

# DC electricity production (kWh/m2 floor area)*

Yellowknife

Iqaluit

Montreal

2

6.21

6.28

5.90

3

6.22

6.29

5.90

4

4.79

4.84

4.41

image494

Scenario

Fig. 6 Building heating and cooling loads for the 5 scenarios.

2. Conclusion

This study showed that double-glazed and triple-glazed BIPV curtainwalls with a PV laminate used as the outer pane have similar electrical performance. When a PV laminate is used as the middle pane in a naturally ventilated triple-glazed fenestration system, however, a reduction in electricity generation in the order of 22% can be expected due to the smaller amount or radiation reaching the cells and the heating up of the PV. A possible benefit of this last configuration was found to be the reduction of perimeter heating in the winter caused by greater inner glazing temperature. In locations with important cooling load, however, this temperature could potentially create discomfort in the summer. When using BIPV curtainwalls for the non-vision sections of a south­facing curtainwall facade of a small office building, the heating load was found to increase by 8.9­10.6% for the double-glazed systems and 4.6-5.3% for the triple-glazed ones.

References

[1] M. M. Karteris, K. P. Papageorgiou, A. M. Papadopoulos, (2006). Integrated Photovoltaics as an Element of Building’s Envelope, Int. Workshop on Energy Performance and Env. Quality of Buildings, Greece.

[2] J. Ayoub, L. Dignard-Bailey, W., Richardson, (2003). Promoting Grid-Tied Solar Electricity on Buildings in Canada, SESCI 2003 Conference, August 18-20, Kingston, Ontario.

[3] J. Ayoub, (2006). National Survey Report of PV Power Applications in Canada, International Energy Agency Co-Operative Programme on Photovoltaic Power System.

[4] P. W. Wong, Y. Shimoda, M. Nonaka, M. Inoue, M. Mizuno, (2008). Semi-Transparent PV: Thermal Performance, Power Generation, Daylight Modelling and Energy Saving Potential in a Residential Application, Renewable Energy, 33, 1024-1036.

[5] T. Fung, H. Yang, (2008). Study on Thermal Performance of Semi-Transparent Building-Integrated Photovoltaic Glazings, Energy and Buildings, 40, 341-350.

[6] D. Curcija, W. P. Goss, (1995). New Correlations for Convective Heat Transfer Coefficient on Indoor Fenestration Surfaces — Compilation of More Recent Work, ASHRAE/DOE/BTECC Conference, Thermal Performance of the Exterior Envelopes of Buildings VI.

[7] R. J. Cole, N. S. Sturrock, (1977). The Convective Heat Exchange at the External Surface of Buildings, Building and Environment, 12, 207-214.

[8] J. L. Wright, (1996). A Correlation to Quantify Convective Heat Transfer between Vertical Window Glazings, ASHRAE Transactions, 102, Pt. 1, 940-946.

[9] ASHRAE, (1998). Standard Method for Determining and Expressing the Heat Transfer and Total Optical Properties of Fenestration Products, Public Review Draft of Standard 142P, American Society of Hating, Refrigerating and Air Conditioning Engineers, Atlanta.

[10] Y. Poissant, L. Couture, L. Dignard-Bailey, D. Thevenard, P. Cusack, H. Oberholzer, (2003). Simple Test Methods for Evaluating the Energy Ratings of PV Modules Under Various Environmental Conditions, Proc. 2003 ISES Solar World Congress, Junte 14-19, Goteborg, Sweden.

[11] SEL (Solar Energy Laboratory), (2005). TRNSYS 16 — A Transient System Simulation Program, University of Wisconsin, Madison, Wisconsin.

[12] D. E. Holte, (1995). A Parametric Study of the Impact of High Performance Windows (and Curtain Walls) on Building Heating and Cooling Loads, Energy Use & HVAC System Design, Conf. Proc. Window Innovation’95 Toronto, Canada, June 5-6, 500-508.

[13] Enermodal, (2001). FRAMETMplus 5.0 developed for Natural Resources Canada.

[14] Natural Resources Canada, (2005). RETScreen Int. 4.0 — Clean Energy Project Analysis Software.

[15] Caneta Research Inc, (2001). Development of Generic Office Building Energy Measures, Report prepared for Public Works and Government Services Canada.

[16] National Research Council Canada, (1997). Canadian Model National Energy Code for Buildings 1997.

Nomenclature

Symbols

cv

Convective

Specific heat at constant pressure (kJ/kgK)

g

Glazing

c

Specific heat at constant volume (kJ/kgK)

gnd

Ground

F

View factor (dimensionless) 2

i

Inner

h

Heat transfer coefficient (kJ/hm2K)

in

Inlet

H

Window height (m)

Li

PV laminate glazing facing indoor

m

Mass flow (kg/h)

Lm

PV laminate middle layer (PV+EVA)

Ppy

PV cells power (kJ/hm2)

Lo

PV laminate glazing facing outdoor

R

Thermal Resistance (hm2K/kJ)

o

Outer

t

Thickness (m)

out

Outlet

T

Temperature (K)

rd

Radiative

S

Absorbed solar energy (kJ/hm2)

sky

Sky

W

Window width (m)

sur

Surroundings

Subscripts

Greek symbols

a

Air cavity

є

Emissivity (dimensionless)

amb

Ambient

P

Density (kg/m3)

cd

Conductive

a

Stefan-Boltzmann constant (kJ/hm2K)

Economic evaluation

In order to extend the evaluation from ecological to economical aspects, investments and running costs (cleaning, energy, maintenance etc.) have to be considered as well. The evaluation system offers an EXCEL tool for calculating cost indices according to the morphological box, based on costs of fa? ade components. For purposes of overall judgement the cost indeces can be transformed to marks comparable to the energetical indices.

1.2. Comprehensive evaluation

Finally the separate energetic and economic evalutions can be combined to a comprehensive judgement by the user. For the different aspects of the evaluation relative weights have to be determined by the user. This allows him to stress certain criteria in an individual manner for a certain purpose. A building investor, e. g., will have preferences differing from those of a building owner who intends to occupy the building.

1st International Congress on Heating, Cooling, and Buildings — 7th to 10th October, Lisbon — Portugal /

image380

Fig. 4. Comprehensive evaluation of three fagade systems 3. Additional Applications of Energy Assessmant, Outlook

Currently the eveluation system is an EXCEL tool by which fagade parameters can be classified only stepwise within certain bandwidths. The next target is to develop a tool, which allows a stepless, continuous definition of input parameters. First tests have proved that the output of energetical data can be derived by a five dimensional intepolation tool. There was developed a free choice of interpolation for properties by regession analysis. Thus an unbounded design variety can be evaluated quickly, based on a limited number of elaborate simulations.

The assessment system was initially developed for an application by clients in early design stages. During the process of development there has been discovered a large potential of additional applications. The assessment method might be used by designers and consultants as well in early and advanced design stages for purposes of control and/or optimazation of certain aspects.

The Diploma thesis of Preibler [2] gives an example for the advanced energetical analysis of fagade systems. One objective was to visualize the influence of the five physical design parameters on the energy demand. Three dimensional diagrammes (Fig. 5) and vector-analysis can help to catch the influence on one glance.

Another application of the assessment tool might be to generate facade designs under given boundary conditions. More research is necessary to gain the full potential of energy assessment systems for an improvement of the design process.

A

image381

Parameter 1

Fig. 5. Total primary energy demand for a given variation of parameters

References

[1] Gralla, Mike, Muller, Helmut: Unpublished research report for Bundesamt fuer Bauordnung; „Bewertung von Glasfassaden unter Berucksichtigung von Kriterien der Enrgieeinsparung und Wirtshaftlichkeit“, (2008)

[2] Preissler, Andreas: Diploma thesis “Einfluss von Fassadenparametern auf den Gesamtenergiebedarf von Gebauden”, Lehrstuhl Klimagerechte Architektur, TU Dortmund, (07/2008)

Winter thermal behaviour

The Health Sector has a large glazed area facing the North that collects direct solar radiation in winter. The hourly sunlight projection on the wall of the North corridor entering through a window of the Health Sector, is shown in Fig. 4 for a winter day. The projection was calculated through the

image423

image424

software LuzSol [5], developed at Universidade Federal de Sao Carlos, Brasil. The openings are 2m width and 1m high. Because solar radiation reaches the half bottom of the wall most of the day, a dark colour painting is Fig. 4. Sunlight projection on a North wall recommended to increase the absorbed solar energy in of a window in the Health Sector (winter). winter.

Подпись: (b)(a)

Fig. 5. Hourly thermal behaviour of the Health Sector in typical winter day. (a) North and central thermal

zones; (b) South thermal zones.

The hourly thermal behaviour of the Health Sector is shown in Figs. 5 (a) and (b) for the North, central and South thermal zones. For a mean outdoor temperature of 10.7°C, the North corridor reaches a mean temperature of 15°C, with a maximum of 19 °C at 14PM (solar hour). The mean temperatures of the central offices are around 13°C, requiring small conventional air heaters to reach the comfort zone. The thermal swings are 8°C in the North corridor and 6°C in the offices. All zones facing South will require auxiliary heating (Fig. 5b). Only in clear sky days, when the solar irradiance reaches 10.6MJ/m2, the offices will not require auxiliary heating (Fig. 6a). A possibility to heat the central offices would be the use of the North corridor as a sunspace from which the hot air could be introduced by natural convection into the offices through little openings in the wall, that should be mechanically closed during the night.

This strategy was evaluated by the simulation of the building in a clear sky day. Two openings were considered in each office, one at floor level and the other at 2m height, near the ceiling. The openings sizes were 0.75m x 1m, that is, a 1% of the office wall area. When the vents are open (Figure 6b), the air temperature of the corridor and the offices are 1 °C lower and 1°C higher, respectively, than in Fig. 6a. Because the temperature in the corridor is still high, extract fans could be added to remove the air of the corridor and blow it within the doctors offices.

(a) (b)

Fig. 7 Hourly outdoor temperature, solar irradiance on horizontal surface (W/m2) and hourly temperature of
the thermal zones in the Development Sector for a winter day. a) Original design, b) an additional roof

clerestory.

In those days when the solar radiation approaches the monthly daily average value (7.93 MJ/m2), it will be necessary auxiliary heating because the direct solar gains are not sufficient to reach the thermal comfort. For any solar radiation value, southern rooms always require auxiliary heating.

The Development Sector needs auxiliary heating during the winter, because the solar heat gain is mostly collected only on East windows (the West windows are shaded by the surrounding buildings). Figure 7a shows the hourly thermal behaviour of this Sector: when the mean outdoor temperature is 10.7 °С, the mean indoor air temperatures are around 11.7 °C with thermal swings of 5°C. Between 10:00AM and 16:00PM, the outdoor air temperature is higher than indoors, and the maximum temperature is reached at 14:00PM. The office of the social assistant is the warmest

local because it is small and it collects direct solar gain, whereas the more cold local is the storeroom, that does not have direct solar gain. To reduce the auxiliary heat load in winter, two options were tested: an increase of the solar collection through clerestories in the roof, and a lowering of the thermal losses through the roof. The simulation of the first option, that is, the addition of glazed areas facing North in the roof showed no significant increase of the indoor air temperatures. The second tested option was the addition of a tight air chamber in the roof (with ventilation in summer), between the metal sheet and the thermal insulation. The results are shown in Figure 7b: in this case, with an outdoor mean temperature of 10.7°C, the indoor mean temperature is around 12.7 °С. Also it was observed that diurnal temperatures of several rooms increased behind the outdoor temperature. A greater indoor thermal amplitude is not a problem since the thermal behaviour of the building was significantly improved during the occupation hours. For example, the daily thermal amplitude of the classrooms is 9 °С, but during the occupancy period (8 AM to 20PM) it is around 5°C and the mean temperature is 15°C.

Solar Bicycle Lighting

In the bicycle market, battery powered lighting is more and more common. A disadvantage of battery powered lighting is that the battery has to be replaced frequently. This can be avoided by using PV solar energy. The battery will then recharge itself and battery replacement is only necessary when the battery is worn out, after 3 to 4 years. The bicycle light designed in this project
makes use of a separable battery pack. The battery pack houses the PV panel and the battery, which means that it can charge separate from the bicycle on a location with higher irradiance than where the bicycle is parked. An additional advantage of the battery pack is that it can be used for other applications. Conversations with bicycle light manufacturers indicated that they are interested in designing bicycle lights that make use of the battery pack.

image464

Fig. 7. PV battery pack in the bicycle light (left) and the battery pack (right)

Problems in Operation

Actually, there are two major problems we could see in our projects. The first one is related to the interface to the distribution of chilled water in the buildings. Quite often flow of distribution is not balanced and optimized, return temperatures are very low and need careful evaluation already in the engineering but affect significantly operation. Otherwise the absorbtion chiller runs in modes very close to freezing temperatures that possibly can affect the chiller, however, adjusting existing systems can be a serious challenge.

Second, we can report some problems with the cooling towers that are not specifically connected to the solar system but typical for open cooling towers. Blocked flow and insufficient water supply caused a stop of a system several times.

Besides that, the systems are very stable and could overcome blackouts and other human impacts surprisingly easy.

Description of calculation methodologies

In this work only thermal solar systems which are pre-heat or solar only systems for preparation of hot water are considered, since this is the case where the Portuguese regulations [1] imposes a specific calculation methodology [2].

1.1 European Standard EN 15316 (part 4-3) Methodology

The objective of this series of European Standards is the calculation of system energy requirements and system efficiencies. According to the standard, for thermal solar systems, the heat balance corresponds to the schematic representation of Fig.1 (for pre-heat/solar only systems). In this figured the terms relevant for comparison with SolTerm [2] are signalled in red. Only hot water preparation is relevant for this purpose. The input, Esolin, for purposes of comparison, was determined by the SolTerm data base.

image397

Fig. 1- Heat Balance for solar pre-heat system/solar-only system (according to EN 15316-4-3). The terms

relevant for the present work are signalled in red.

 

In this short description, the nomenclature of the standard will be used. In some situations, clarification of the terms is need since they do not correspond to the common solar thermal vocabulary according to EN ISO 9488 [4]. This is the case of the term “auxiliary”, which the standard uses for the electrical energy for pumps and controllers and for which the Solar Energy Vocabulary (EN ISO 9488) [4] uses the term “parasitic energy”.

The main objective of the standard EN 15326-4-3 [3] is the calculation QHW, sol, out, i. e., the total heat delivered by the thermal solar system to space heating and domestic hot water distribution system. As already stated, the present discussion will be centred on the calculation of QW, sol, out . Two methods are considered for this calculation:

— Method A uses the results of tests performed to Factory Made Systems according to EN 12976-2

[5] .

— Method B uses as input data the solar thermal system component data, i. e. system dimensional characteristics and data from component test and state of the art knowledge, such as:

Collector parameters: collector aperture area, zero-loss efficiency, heat loss coefficients;

Collector loop thermal losses and thermal losses of the distribution between storage tank and the distribution system (length of pipes, insulation and efficiency);

Climatic conditions: solar irradiation, outdoor air temperature;

Thermal losses of the solar storage tank

Storage tank parameters: type of storage tank, size;

In this paper all comparisons are performed considering the method B, based on the f-chart method

[6] . The general calculation of solar output is given by the expression:

=(a + bX + cY2 + dX2 + e¥3)-о, Лш„ [KWh] (1)

Where Qsolusm is the monthly heat use applied to the thermal solar system [kWh], usually termed

as heat demand. a, b, c, d, e are correlation factors depending on system configuration[8] and X and Y are dimensionless factors.

The term Qsohout, m represents the monthly values of QW solout For the determination of X the following equation is used:

X = A ■ Uloop ■ Л loop ■ AT ■ fst ■ tm /(Qsol, us, m ‘ 1000) (2)

In this expression of X, the term AT is a reference temperature difference calculated according to:

AT = Є„, — Q. ae [K] (3)

The heat loss coefficient of the collector loop, i. e., collectors and pipes, is determined by the collector characteristics and the insulation of the pipes. The heat loss loop coefficient is calculated by:

Uio0p = a1 + a ■ 40 + Ul0op, p / A [W/(m2.K)] (4)

The value Y is calculated according to eq. 5. It depends on the collector data (zero-loss collector efficiency) and the solar irradiance on the collector plane:

Y = A ■ IAM ■ Ло • Aioop ■ Im ■ tm /feoum •1000)

The term Qsoi, us, m is calculated considering the daily load volume, a fixed load temperature and a fixed cold water temperature:

Qsol, us, m Vload’P’Cp'(Tload (6) with p=1kg/litre and Cp = 4187 kJ/kg°C.

For some of the above parameters, the standard suggests default values. The values considered in the comparison were chosen either in accordance with the default values of EN 15316-4-3 or with those considered in SolTerm [2]. For determination of the thermal solar system output, care has to be taken in order to consider only Qsol, out, m < Qsol, use, m and Qsol, out, m > 0.

Towards the implementation of the Passive houses in the Portuguese context

L. Brotas1, G. Carrilho da Gra^a2, H. Gonsalves1*, M. Lerer2 and P. Paredes2

1 INETI, Department of Renewable Energy, Campus do Lumiar do INETI, 1649-038 Lisbon, Portugal
2 Natural Works, Rua Ricardo Espnito Santo N7 CV-E, 1200-790 Lisbon, Portugal
* Corresponding Author, helder. goncalves@ineti. pt

Abstract

Achieving a pleasant indoor environment with low energy consumption is a major goal of good building design. Overheating, in particular, is a problem in southern European climates, where several approaches to achieving comfortable indoor conditions, while keeping the building’s energy consumption low, have been successfully established. The Passivhaus standard, developed in Germany, defines requirements for very-low energy homes with regards to space heating. The strategies adopted in cold climates consist of a highly insulated envelope combined with reduced air losses and a mechanical ventilation system with heat recovery. This approach reduces the heating needs and high thermal comfort levels can be achieved with improved energy efficiency. The Passive-On project has taken this concept further by also looking at the warmer European climates where the cooling loads may become a major issue. The project consortium has therefore formulated a revised proposal for the application of the standard to those climates. This paper presents part of the results of this European funded project.

Keywords: Low energy buildings, Passivhaus, passive cooling, adaptive comfort

1. Introduction

In Europe, buildings are responsible for 40% of the final energy consumed. In Portugal, this percentage is lower, 17% domestic and 12% services (2006). However, the energy consumption is still increasing, in particular related to cooling systems. Within this context, the European Commission presented the directive EPBD which focused on the energy performance in buildings. Moreover, recent concerns about the security of the energy supply and the rising price of oil, make energy efficiency a top priority, as well as to diversify the energetic resources, promoting the adoption of renewable energies to reduce the exterior energy dependency and GEE emissions. [1]

More broadly, the European Parliament resolution of 31 January 2008 on an Action Plan for Energy Efficiency: Realising the Potential “calls on the Commission to propose a binding requirement that all new buildings needing to be heated and/or cooled be constructed to passive house or equivalent non-residential standards from 2011 onwards, and a requirement to use passive heating and cooling solutions from 2008”. [2]

Other countries of Europe have standards such as the Code of Sustainable Homes in England and Wales where level 5 corresponds to the Passivhaus standard, to be enforced by 1912. This standard also requires all homes to be zero carbon (level 6) by 2016, having to produce on-site energy. [3]

Lighting index Cm according to the orientations of openings

Figure 4 presents the results of the lighting index for different d/h ratio and for two different opening azimuths. d represents the length of the overhang and h the height of the window. These values of Cm are also compared to the PERENE requirements.

One can notice that the objectives of PERENE are too difficult to meet. We have assumed that the glazing has a transmittance equal to 1 (the window is opened if it is used in natural ventilation). PERENE requires values of Cm of 0,3 and 0,25 for windows facing North and West respectively.

Values of Cm of 0,3 and 0,5 are respectively demanded for openings oriented East and South. Only a d/h ratio of 1.5 could allow to meet PERENE for an East-oriented window.

To meet acceptable values of Cm, it would be necessary to reduce the transmittance of the glazing, what is not possible if this one is used in natural ventilation. It would be necessary to reconsider the requirements of the PERENE standard, at least for this type of solar shading

image470

Figure 4: Values of lighting index Cm for different d/h ratio and for North and West oriented windows. d represents the length of the overhang and h the height of the window

image471

Figure 5: Values of lighting index Cm for different d/h ratio and for East and South oriented windows. d represents the length of the overhang and h the height of the window

Simplified integration of PV in sealed glazing windows. — development and demonstration of a complete system

XP. Haugaard, 2D. Aara, 3P. Poulsen, 3B. Bentzen, P., 4P. M. Nielsen and 4J. Andersen

1 Esbensen Consulting Engineers A/S, Gammel Koge Landevej 22, 2500 Valby, Denmark
2 Gaia Solar A/S, Hammerholmen 9-13, 2650 Hvidovre, Denmark
3 FAKTOR 3 ApS, Vesterbrogade 24b 2. sal, 1620 Kobenhavn V, Denmark
4 Idealcombi A/S, Norre Alle 51, 7760 Hump, Denmark
* Corresponding Author, p. haugaard@esbensen. dk

Abstract

The project group is developing a low-cost PV-window for building owners and architects to use in building designs for both new and retrofit buildings. With a U-value of 1.20 W/m2K the developed PV-window fulfills the requirements within the Danish Building Regulation and as a bonus it produces electricity to the building.

Architects have found the PV-window interesting to use in building designs hence it offer many different possibilities to regulate the thermal indoor climate, daylight penetrations, reflections and communications. Tests have shown, depending on the design and layout of the PV-pane, that the PV-window can supply sufficient daylight to buildings.

The PV-window addresses the field of making energy right buildings using the energy falling on the buildings to supply itself in a fully integrated an aesthetical way and not as an add-on to buildings. It helps reducing the need for primary energy and gives the building a clearly environmentally green profile.

The development of this product has not been completed and will continue.

Keywords: PV-window, Building Regulation, low cost, custom design

1. Introduction

1.1 Scope

From the proactive strategy of reducing prices on integrated PV-systems the project aims to develop a PV-window which is cheaper than and technical fully compatible with the existing relative expensive standard PV-panels. Hence it is also the aim to develop an elegant PV-window solution that integrates architecture, aesthetics and flexibility in its design thus becoming an elegant attractive solution for both new and retrofit buildings. The PV-window must apply to the current Building Regulations in Denmark which has been tightened in 2006.

1.2 Objective

It is the objective to reduce the price on the PV-window by up till 20 % or more compared to similar products, fulfill the Danish Building Regulation, integrate, demonstrate and test the PV- window in an actual building and learn how it influences on thermal indoor climate in spaces.

The project is a part of the Danish PSO-F&U scheme sponsored by Energinet. dk.