Energy performance

image127 image128 image129 Подпись: (Equation 1)

From a simple energy balance for the thermally driven chiller, the specific primary energy consumption of the dry cooler and the cooling tower per unit of heat rejected, PEspec, cooling tower, including the electricity needed for the circulation pump of the cooling water cycle, can be expressed as follows:

In this equation Espec, coolin tower is the specific electricity demand of the cooling tower per unit of cooling energy (heat rejection) including the circulation pump of the cooling water cycle and it is expressed in kWhel/kWh

cooling, [13].

In addition to the above defined specific energy consumption, the total cooling energy produced by the chiller, the electricity consumption of the fans and the water consumption were calculated with TRNSYS and reported in Table 2. The simulations were conducted for an entire cooling season, (middle of June to middle of September).

Bolzano

Roma

Palermo

Air-cooled

Cool tower

Air-cooled

Cool tower

Air-cooled

Cool tower

Qsol inc [k^Wh-]

35140

35140

42350

42350

42980

42980

Qsol gain[k Wh]

13550

16047

18680

21744

19402

22456

Qeva [kWh]

8109

9035

11634

12977

11991

13216

Qheat reject [k~Wh]

20144

25581

29047

35819

30135

36903

COP [-]

0.67

0.72

0.67

0.71

0.66

0.70

Enele [kWh]

480

150

689

224

734

237

Evaw [m3]

28.35

40.43

41.21

Espec, heatrej

[kWhel/kWhheatr]

0.024

0.0058

0.024

0.0062

0.024

0.006

PEspec, heatrej

[kWhpE/kWhheatr]

0.148

0.035

0.148

0.037

0.153

0.037

Table 2. Energy performance