Constant regeneration humidity

Подпись: 10 20 30 40 50 60 70 80 90 100 Inlet Relative Humidity (%) Подпись: Inlet Relative Humidity (%)

The results of experimental testing at varying supply inlet temperature and inlet relative humidity for different regeneration temperatures at constant regeneration humidity are shown in the following graphs.

Figure 4. Moisture removal in supply air stream for Figure 5. Moisture removal in supply air stream for varying supply inlet humidity and temperature at 50°C varying supply inlet humidity and temperature at 80°C regeneration temperature. regeneration temperature.

Figure 4 shows the moisture removal from the supply air stream at varying relative humidity and temperature for a regeneration temperature of 50 °С. It is obvious that the moisture removal increases with both increasing relative humidity and temperature of the supply air. The maximum moisture removal for supply inlet conditions of 40°C/95% RH was measured at 17 g/kg d. a.. In this point the driving temperature difference is only 10K between supply and regeneration air, however the difference in absolute humidity between supply and regeneration air is 40 g/kg d. a..

The same parameters as in Figure 4 are shown in Figure 5 for a regeneration temperature of 80°C. It can be observed that the moisture removal at 80°C regeneration temperature is generally greater than at 50°C regeneration temperature. A larger moisture removal capacity is clearly noticeable in Figure 5 at high supply inlet humidity and supply inlet temperatures of 30 and 40°C. However, at supply inlet temperatures of 10 and 20°C the difference in moisture removal between 50 and 80°C regeneration temperature is relatively small. In fact, the difference in moisture removal between 50 and 80°C regeneration temperature for supply inlet temperatures between 10 and 30°C and supply inlet relative humidity between 20 and 50% is smaller than 1 g/kg d. a. This shows that a regeneration temperature of 50 °C can almost achieve the same moisture removal at lower inlet humidity supply air.